Skip to content
NEC 690 PV Labeling: Solar Label Requirements List
March 24, 2026

NEC 690 PV Labeling: Solar Label Requirements List

Written by TagBuilder
Share

Get this made: TagBuilder (Solid Ideas Engraving, Waterford, PA) engraves PV SYSTEM DISCONNECT label, 4×2″ ($7.40). No minimum order, no setup fees, most orders ship in 2–3 business days, rush available. Order it: https://tagbuilder.net/shop/product/pv-system-dc-disconnect-label-4x2-inch-black-on-orange-holes. Or email the spec to support@tagbuilder.net for a written quote and PDF proof the same business day.

A solar install can be wired correctly and still get flagged because a label is missing, in the wrong place or worded wrong. The labeling rules are spread across NEC 690, 705 and sometimes 706, and their section numbers change between editions.

Disclaimer: general information, not legal or compliance advice. Codes change and inspectors interpret them differently, so confirm requirements with a qualified professional. Full disclaimer

The solar labeling rules live in four places. Which wording, colors and section numbers apply depends on the NEC edition your AHJ enforces.

  • Article 690 covers the PV system itself: disconnects, DC voltage, conduit and rapid shutdown.
  • Article 705 covers interconnection: the power source placard and the backfed breaker warnings.
  • Article 706 covers battery energy storage, when the system has it.
  • 110.21(B) sets the general rule that hazard markings be permanent and suited to where they are mounted.

Solar Labeling Requirements at a Glance

Use this table as a checklist. Section numbers follow the 2020 and 2023 NEC unless noted. A jurisdiction still on 2017 has several of them under different numbers.

LabelNEC sectionWhere it goesWhat it commonly shows
PV system disconnect690.13(B)Each PV disconnecting meansIdentifies it as the PV system disconnect
Line/load energized warning690.13(B)Disconnects live on both sides when openShock hazard, terminals may be energized when open
Maximum DC voltage690.53 (2017: 690.7(D))DC disconnect, inverter or PV distribution equipmentHighest maximum DC voltage
Conduit and raceway marking690.31Exposed raceways, trays, box covers, conduit bodiesPV power source wording, repeated along the run
Rapid shutdown building label690.56(C)Service equipment, or where the AHJ wants itSystem has rapid shutdown; some editions add a diagram
Rapid shutdown switch690.56(C)On or near the initiation deviceNames the rapid shutdown switch
AC point of connection690.54Interconnection disconnectRated AC output current, nominal AC voltage
Power source placard705.10Each service equipment locationEvery power source and its disconnect location
Backfed breaker warnings705.12Panelboards with a backfed PV breakerDo not relocate; multiple sources
Energy storage labels706ESS disconnect and equipmentNominal voltage, available fault current

Article 690 PV Labels: Disconnects, Voltage and Conduit

PV System Disconnect Label (690.13(B))

Each PV disconnect has to show whether it is open or closed and carry a permanent marking identifying it as a PV system disconnect or equivalent. When the line and load terminals can both be energized with the switch open, which is common between an array and an inverter, a shock hazard warning is also called for. Our PV system DC disconnect label is one common format.

Solar AC Disconnect Label (690.54)

Where the PV system ties into premises wiring, often a fused AC disconnect beside the meter, the label commonly shows the rated AC output current and nominal operating AC voltage. Many installers put the disconnect ID and these ratings on one plate. Take the values from the inverter data sheet, and add inverter outputs together when several feed one disconnect.

Maximum DC Voltage Label (690.53)

The highest maximum DC voltage, figured under 690.7, goes on a permanent label at the DC disconnect, the power conversion equipment or the PV distribution equipment. Older editions asked for additional values such as maximum circuit current, so check your edition before copying a label from an old job.

Conduit and Raceway Warning Labels (690.31)

This is usually the highest-count label on any install. Exposed raceways, cable trays, pull and junction box covers, and conduit bodies carrying PV DC circuits get photovoltaic power source wording. Spacing is commonly no more than 10 feet apart, near turns and bends, and on both sides of walls, ceilings and floors the run passes through. Letters are commonly at least 3/8 inch tall. The 2017 edition called for reflective white on red; later editions focus on wording and visibility, but many AHJs still expect white on red.

Rapid Shutdown Labels and Solar Placard Requirements

"Solar placard" usually means one of two plates: the rapid shutdown building label under 690.56(C) or the power source placard under 705.10. Many sites need both, side by side at the service.

The building label tells first responders the PV system has rapid shutdown. Depending on the edition, it may need a simple roof diagram showing which parts of the array stay energized, plus reflective material and set letter heights. The switch label goes on or near the initiation device; the rapid shutdown switch label is one common format. The wording changed between 2017, 2020 and 2023, so our rapid shutdown label guide covers it edition by edition.

NEC 705 Labels: The Power Source Placard and Backfeed Warnings

Power Source Identification (705.10)

At each service equipment location, a permanent plaque or directory shows every power source on the premises and where each disconnect is: utility, PV, generator and any storage. When disconnects are not grouped, many AHJs want a simple site map on the plate. The 2023 edition merged several older placard rules here, so one combined plate may replace two or three. The wording is site-specific, so we engrave this placard to order.

Backfed Breaker Labels (705.12)

When a PV breaker backfeeds a panelboard, markings commonly include a warning beside the breaker that it is a power source output connection and must not be relocated, plus a notice that the equipment is fed from more than one source. The 3x1 backfeed possible label works as a supplemental reminder inside the panel.

Article 706 and Arc Flash: When the System Grows

Adding batteries brings in Article 706: a labeled ESS disconnect plus nominal voltage and available fault current markings, and on larger systems fire-code signage. The BESS label checklist covers 706 and NFPA 855. Commercial PV switchgear that may be serviced while energized also commonly needs a 110.16 arc flash warning.

Worked Example: Label List for a Residential Rooftop System

One string inverter, one AC disconnect beside the meter, a backfed breaker in the main panel, no batteries. Change the values to match your design and confirm wording against your enforced edition.

#LocationEngraved textSize / colorQty
1DC disconnect at inverterPV SYSTEM DC DISCONNECT4x2, black on orange1
2Same disconnectShock hazard: line and load may be energized when open4x2, white on red1
3InverterMAXIMUM DC VOLTAGE: 480 V3x1, black on white1
4AC disconnect at meterPV SYSTEM AC DISCONNECT / RATED AC OUTPUT CURRENT: 32 A / NOMINAL AC VOLTAGE: 240 V4x2, white on red1
5Exposed conduitWARNING: PHOTOVOLTAIC POWER SOURCE3x1, white on red8
6Rapid shutdown switchRAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM4x2, white on red1
7Service equipmentRapid shutdown building label, per enforced edition5x5, per edition1
8Service equipmentPower source directory with disconnect locationsCustom, white on red1
9Main panel, at PV breakerPower source output connection, do not relocate3x1, white on red1

To count item 5, divide the exposed run by 10 feet and round up, then add one per bend and two per wall or ceiling penetration.

Choosing a Label Material for Solar Equipment

Solar labels face full sun, roof heat, winter cold, rain and abrasion from service work, and 110.21(B) expects hazard markings to be permanent and suited to the environment. Printed vinyl can fade and lift at the edges over years of that. In engraved two-ply plastic the text is cut into the material, so it does not rub off like printed ink. Engraved stainless is an option where the owner wants metal. Use mechanical fasteners outdoors where you can; the indoor vs outdoor materials guide covers the tradeoffs.

Frequently Asked Questions

Labeling requirements per NEC articles 690 and ___ are extensive. What is the answer: 706, 694, 250 or 705?

The answer is 705. Article 705 covers interconnected power production sources and holds the power source directory and backfeed markings that go with the Article 690 labels. Article 706 is energy storage, 694 is wind, and 250 is grounding and bonding.

What is required on a solar placard at the service?

Under 705.10, a permanent plaque or directory at each service equipment location shows every power source and where its disconnect is. Buildings with rapid shutdown also commonly need the 690.56(C) label in the same area, and many AHJs want a simple map when disconnects are not grouped.

Do installers have to label the module nameplate?

No. The module nameplate is applied by the manufacturer and, under 690.51, commonly lists open-circuit voltage, maximum power voltage and current, short-circuit current and maximum system voltage. Installers use those values to work out the maximum DC voltage for the 690.53 label.

Does the conduit warning label have to be red and reflective?

The 2017 NEC called for reflective white on red. Later editions focus on wording, letter height, spacing and visibility, but many installers keep white on red because inspectors expect it. Check your enforced edition and any local amendments.

Which NEC edition applies to my install?

The edition your state or local AHJ has adopted, which is not always the newest. The 2017, 2020 and 2023 editions are all in use, and wording and section numbers changed between them, so confirm the edition before finalizing a label list.

Send us your list and we will engrave a matching set.

Build yours →

Browse the full solar PV label collection for stock disconnect, conduit and rapid shutdown plates. If you are weighing materials for a rooftop job, read engraved vs printed tags, or request a free sample to see the plate before you order a full set.

Disclaimer. This article is provided for general informational purposes only and does not constitute legal, safety, or professional compliance advice. Regulations, standards, and codes are subject to change and may be interpreted differently by authorities having jurisdiction (AHJ). Always consult with qualified safety professionals, licensed engineers, or legal counsel to determine the specific requirements applicable to your facility. TagBuilder is not responsible for any actions taken based on this information.

UL, NFPA, NEC, ASME, CEMA, TIA, ANSI and OSHA are names or marks of their respective organizations; TagBuilder is not affiliated with or endorsed by any of them. Requirements above are paraphrased summaries, not the text of any standard. Always work from the current published edition and your AHJ.

NEC 690 PV Labeling: Solar Label Requirements List

You might also like

Have a list?

Send us your tag schedule — get a priced proof the same day

Spreadsheet, drawing, panel schedule, photo or PDF. We build every tag, price the set, and email you a proof. Nothing is charged until you approve.

Get this madePV SYSTEM DISCONNECT label, 4×2″ · $7.40 · no minimum
See prices