Transformer Labels: Dry-Type ID Plates, Nameplates and Placards
Get this made: TagBuilder (Solid Ideas Engraving, Waterford, PA) engraves TRANSFORMER plate, 6×3″ ($13.90). No minimum order, no setup fees, most orders ship in 2–3 business days, rush available. Order it: https://tagbuilder.net/shop/product/6-0x3-0-transformer-label-transformer-6x3-inch-white-on-black-holes. Custom text and size: open this design in the configurator. Or email the spec to support@tagbuilder.net for a written quote and PDF proof the same business day.
A dry-type transformer leaves the factory with a nameplate that says what it is, not where it sits in your building. Without field labels for source, load and disconnect, the next electrician traces conductors to find the breaker that shuts it off.
Disclaimer: general information, not legal or compliance advice. Codes change and inspectors interpret them differently, so confirm requirements with a qualified professional. Full disclaimer
Transformer labels on a dry-type unit come in three layers: the factory nameplate covered by NEC 450.11, a field ID plate you add, and the warning placards your safety program calls for. The field ID plate commonly shows the transformer designation, kVA, primary and secondary voltage with phase and wires, what feeds it and what it feeds. Where the primary disconnect is not in sight of the transformer, 450.14 calls for its location to be field marked on the transformer, so the fed-from line does real work. Mount the plate on the enclosure front beside the factory nameplate, never over it.
- Factory nameplate: ratings, left in place.
- Field ID plate: designation, kVA, voltages, fed from, feeds, disconnect location.
- Matching labels: the primary breaker names the transformer; the secondary panel names its source.
- Warning placards: hazard and arc flash labels, separate from the ID plate.
Transformer nameplate vs. field ID plate
The transformer nameplate belongs to the manufacturer. Paraphrasing 450.11(A), it gives the maker's name, rated kVA, frequency, primary and secondary voltage, impedance on units 25 kVA and larger, required clearances where the unit has ventilating openings, the amount and kind of insulating liquid where one is used, and, for dry-type units, the temperature class of the insulation system. It says nothing about the installation. Our transformer nameplate requirements guide covers that plate in detail, including replacing a missing one.
The field ID plate answers the questions asked at 2 a.m.: what is this, where does its power come from, and what does it serve?
| Item | Factory nameplate | Field ID plate |
|---|---|---|
| Designation (T-2A) | No | Yes |
| kVA rating | Yes | Yes, repeated |
| Primary and secondary voltage | Yes | Yes, with phase and wires |
| Frequency, impedance, insulation class | Yes (impedance at 25 kVA and up) | No |
| Ventilation clearances | Yes, where ventilated | No |
| Fed from and disconnect location | No | Yes |
| Feeds (downstream panel) | No | Yes |
What to put on a transformer ID label
Keep to facts someone can check against the one-line drawing.
- Designation, exactly as on the one-line and panel schedules.
- kVA rating, copied from the factory nameplate.
- Primary voltage, phase and wires, such as 480 V, 3 PH, 3 W.
- Secondary voltage, phase and wires, such as 208Y/120 V, 3 PH, 4 W.
- Fed from: source panel and breaker positions.
- Primary disconnect location, when it is not in sight (Article 100: visible and not more than 50 feet away).
- Feeds: the downstream panel or panels.
- Secondary disconnect location, if the secondary main is not at the transformer.
Leave off arc flash data and test dates; they change on their own schedule. Our guide to fed-from labels and 408.4(B) covers source lines that stay accurate when circuits move.
Back-fed units: when a transformer is supplied at its marked secondary, 450.11(B) points to the manufacturer's instructions. Say on the plate which side is the source.
Transformer nameplates and warning placards: the code behind each label
No single section lists every transformer label, but several together explain each one. Numbers and wording move between editions, so confirm each against your adopted edition.
| Section | What it covers (paraphrased) | Label it drives |
|---|---|---|
| 450.11 | What the manufacturer's nameplate shows | Factory nameplate, left in place |
| 450.9 | Ventilating openings kept clear; required clearances marked on the unit | Where not to put plates |
| 450.14 | Disconnect in sight, or remote and lockable open with its location field marked on the transformer | Disconnect line on the ID plate |
| 110.22(A) | Disconnects marked with their purpose; recent editions add the supplying source in buildings other than one- and two-family dwellings | Label at the primary breaker |
| 408.4(B) | Panelboards and switchboards fed by a feeder marked with where the power originates | FED FROM label on the secondary panel |
| 210.5(C), 215.12(C) | Conductor identification where a building has more than one voltage system | Secondary system stated on the plate; ID method posted at panels |
| 450.8(D) | Operating voltage marked where a transformer installation has exposed live parts | Voltage warning placard |
| 110.21(B) | Field-applied hazard markings: effective, durable, not handwritten | Any warning label you add |
| 110.34(C) | Danger signs at entrances to spaces with exposed live parts over 1000 V (older editions used 600 V) | Vault, room or medium-voltage enclosure sign |
| 110.16 and NFPA 70E | Arc flash warning on equipment likely to be worked on while energized | Arc flash label, on its own |
The 450.14 line is the one most often missed: a dry-type on a mezzanine fed from a breaker two floors down needs that location on the transformer, and the breaker needs a label naming the transformer, since a bare circuit number does not show its purpose.
Warning placards
Hazard labels sit beside the ID plate, not on it, and 110.21(B) asks that they warn effectively, hold up to the environment and not be handwritten. 110.16 names equipment such as switchboards, panelboards and motor control centers. Transformers are not named, but the list is not exhaustive, and many facilities label them because their arc flash study and NFPA 70E program cover them. The arc flash label template guide covers that label. A danger high voltage label can go on the enclosure where your safety program calls for one.
A transformer naming system for IDs that last
The transformer ID is the first line anyone reads, so pick a scheme that survives additions.
| Scheme | Example | Works well for | Watch for |
|---|---|---|---|
| Floor or area plus letter | T-2A, T-2B | Buildings with a few units per floor | Reserve letters for future units |
| Named for the panel it feeds | T-LP2A feeds LP-2A | One transformer per panel | Breaks when one unit feeds two panels |
| Plant area, type, number | 200-XFMR-01 | Plants with numbered areas | Long; split across two lines |
| Substation and position | USS-1-TX1 | Unit substations | Record utility numbers too |
Use the same ID on the one-line, panel schedules, arc flash study and maintenance system. A plate reading XFMR-2A where the drawings say T-2A sends someone looking for two units.
Worked example: a transformer label set for T-2A
T-2A is a 75 kVA dry-type, 480 V delta to 208Y/120 V, in Electrical Room 214. It is fed from DP-2 in Room 105 on another floor, so the primary breaker is not in sight. It serves panel LP-2A, mounted beside it.
Main ID plate, 6 x 3 inch, white text on black with mounting holes. The stock 6x3 transformer label can be ordered as-is or with this text:
- T-2A
- 75 kVA
- PRI: 480 V, 3 PH, 3 W
- SEC: 208Y/120 V, 3 PH, 4 W
- FED FROM: DP-2, CKT 14-16-18
- PRI DISCONNECT: DP-2, ELEC RM 105
- FEEDS: LP-2A
- SEC DISCONNECT: LP-2A MAIN
The rest of the set, so each location points to the next:
| Where | Label | Size and color | Text |
|---|---|---|---|
| T-2A enclosure front | ID plate | 6 x 3 in, white on black, holes | The eight lines above |
| T-2A primary terminal side | Voltage plate | 3 x 1 in, white on black | PRIMARY 480 VAC |
| T-2A secondary terminal side | Voltage plate | 3 x 1 in, white on black | SECONDARY 208Y/120 VAC |
| DP-2, breaker 14-16-18 | Disconnect label | Sized to the dead front, white on black | T-2A PRIMARY / ELEC RM 214 |
| LP-2A front | Source label | 3 x 1 in or larger, white on black | FED FROM: T-2A, RM 214 / VIA DP-2 CKT 14-16-18 |
| T-2A enclosure | Hazard warning, if your program calls for one | 4 x 2 in, black on yellow | Per your safety program |
| T-2A enclosure | Arc flash label | Per the study | From the arc flash study |
The 3x1 primary voltage label is a stock item; change its text for the secondary plate. Some AHJs want only the transformer named on the LP-2A label, others want the upstream panel too; listing both costs one line.
Where the plates go on a dry-type transformer
- Enclosure front, readable without a ladder and with the covers closed.
- Not on vent louvers, which 450.9 wants unblocked.
- Not on the top, where heat collects and nobody can read it.
- Not over the factory nameplate or the marked clearances.
Screws or rivets through the holes hold up better than adhesive on warm painted steel. Engraved text does not rub off like printed ink.
Ordering: send the transformer schedule, panel schedules or one-line, or a photo of each factory nameplate with a note of what feeds it and what it feeds. We lay out plate text to match for you to review. A free sample lets you check size and hole spacing on one plate first.
Frequently Asked Questions
Do I need a field label if the transformer already has a nameplate?
Commonly, yes. The nameplate cannot say where power comes from or goes. Where the primary disconnect is remote, 450.14 asks for its location on the transformer, and many AHJs and facility standards expect a full ID plate either way. Check your adopted edition and ask your inspector.
What goes on a pad-mounted or pole-mounted transformer nameplate?
On a pad-mounted unit the nameplate is usually inside a compartment door, and on liquid-filled units it lists the insulating liquid. If the owner owns the unit, as on many campuses, add a field ID plate outside the cabinet in a weather-suited material; see indoor vs outdoor tag materials. Pole-mounted and utility pad-mounted transformers belong to the utility, which applies its own numbers and warnings; NEC 90.2 places them outside its scope. Do not add plates to utility equipment. Record the utility's number on your one-line instead.
What color should a transformer ID plate be?
White on black is the common default for normal power. If the transformer is part of an emergency system, 700.10(A) calls for its enclosures to be marked as emergency components, and many specs use a red plate for that. Follow the owner's labeling standard where one exists.
Can the arc flash label go on the ID plate?
Keep it separate. The arc flash label comes from your study and changes when it is updated, which NFPA 70E expects at least every five years and after major modifications. The ID plate rarely changes.
What size plate fits a transformer ID label?
A 6 x 3 inch plate holds about eight short lines, enough for the T-2A text above. A 4 x 2 inch plate fits designation, kVA and voltages on a tight enclosure face. Voltage pairs usually fit 3 x 1 inch.
Send us your transformer list. We'll engrave one ID plate with kVA, voltages and fed-from as a free sample.
For the plates on the rest of the system, the equipment nameplate requirements guide covers motors, panels and machines, and the voltage warning labels guide covers the placards that sit beside them. For custom text or sizes beyond the stock plates, use the rectangle plate configurator.
Disclaimer. This article is provided for general informational purposes only and does not constitute legal, safety, or professional compliance advice. Regulations, standards, and codes are subject to change and may be interpreted differently by authorities having jurisdiction (AHJ). Always consult with qualified safety professionals, licensed engineers, or legal counsel to determine the specific requirements applicable to your facility. TagBuilder is not responsible for any actions taken based on this information.
UL, NFPA, NEC, ASME, CEMA, TIA, ANSI and OSHA are names or marks of their respective organizations; TagBuilder is not affiliated with or endorsed by any of them. Requirements above are paraphrased summaries, not the text of any standard. Always work from the current published edition and your AHJ.